Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
AAFC
button
Yes
pressed?
No
Count down
AP time
remains?
Yes
No
Quiscent state
Any detector
in alarm?
Yes
AP timer starts
IP timer starts
All detectors
normal?
No
Count down
IP time
remains?
Yes
No
Fire Alarm
in the C.I.E.
Figure 22. Alarm Acknowledgement Facility (AAF) flow chart.
During the AAF process, an AAF alarm will be indicated in the c.i.e.
display ....
.... during the acknowledgement period (AP):
AAF zone xx, activated
.... during the investigation period (IP):
AAF zone xx, investigation in progress
If more than one AAF zones have been activated only the first is
shown in the display.
The detectors in an AAF zone can be one to five and not be
programmed as 2-unit-dependent and not be controlled by the Alert
EBL128 Planning Instructions V1.1.x
No
Yes
94
Buzzer ON
Detector LED ON
AAFC LED ON
Buzzer OFF
Detector LED OFF
AAFC LED OFF
AAFC LED OFF