Panasonic EBL128 Planning Instructions page 28

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
The I/O expansion board 4583 has two programmable supervised or
not supervised voltage outputs (Output 0-1), one programmable
special output (Output 2) for German extinguishing system and five
programmable supervised or not supervised inputs (Input 0-4).
Connections to "J1:1-16" and "J2" according to drawing 128-03 sheet
2/2.
Output 0-1 has to be programmed via Win128 regarding:
 Type, i.e. output for Control, Alarm devices, etc.
 Output signal period (steady, pulse, delay, etc.)
 Supervised / Not supervised
 Logic, i.e. normally low (default) or normally high (24 V DC)
 Control expression (containing one or more trigger conditions)
One to five 33K resistors can be connected. When the connections are
finished, a calibration has to be done. Calibration value has to be in
the range 4K7-50K. See also the EBL128 Operating Instructions
chapter "Calibration of supervised outputs (menu H5/A3)".
Voltage Output 0 (J1:1-2): max. 200 mA (Fuse F1).
(Brandmeldung)
Voltage Output 1 (J1:5-6): max. 200 mA (Fuse F2). "G" FSK öffnen
See also Win128 help or chapter "Programmable outputs", page 61.
Output 2 has to be programmed via Win128 regarding:
Type, i.e. output for Control, Alarm devices, etc.
 Output signal period (steady, pulse, delay, etc.)
 Logic, i.e. normally open (default) or normally closed.
 Control expression (containing one or more trigger conditions)
Output 2 (J1:11-12): Normally open (high resistance, 3K3, when
supervised) or Normally closed (low resistance, 680R, when
supervised). German extinguishing system (Löschanlage).
See also Win128 help or chapter "Programmable outputs", page 61.
Input 0-4 has to be programmed via Win128 regarding:
 Type ("trigger condition")
 Supervised / Not supervised
 Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or Normally closed (low resistance, 680R, when supervised)
 Additional information depending on selected type
26
A normally high output can not be supervised. The supervision voltage is
1.5 – 3.7 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to an activated output.
27
Regarding system voltage, see chapter "Technical data", page 143.
EBL128 Planning Instructions V1.1.x
26
26