Programmable Relay Output (R0); Relay Output For Routing Equipment (Fault Tx) (R1); Programmable Input (I0) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
4.3
4.4
4.5
S1: max. 200 mA (Fuse F6).
See also Win128 help or chapter "Programmable outputs", page 61.

Programmable relay output (R0)

Connections to "J1:17-19" according to drawing 128-23.
The output has to be programmed (via Win128) regarding:
 Type (Control, Fire ventilation, Alarm device, etc.)
 Output signal period (steady, intermittent, pulse, delay, etc.)
 Logic, i.e. normally open or normally closed.
 Control expression (containing one or more trigger conditions).
NOTE!
The output R0 is as default programmed as output for
Routing equipment (Fire brigade tx).
by the LED "Fire brigade tx".
open" or via menu H2/B9. This output can be tested via menu H1, see
the EBL128 Operating Instructions.
See also Win128 help or chapter "Programmable outputs", page 61.
Relay output for routing equipment (fault
tx) (R1)
Connections to "J1:20-22" according to drawing 128-23.
Not programmable relay output.
(Fault tx) is activated during normal operation and will be de-activated
when a fault is generated in EBL128
indicated by the LED "Fault tx activated". This output can be tested
via menu H1, see the EBL128 Operating Instructions.

Programmable input (I0)

Connections to "J1:9-10" according to drawing 128-22.
The input has to be programmed (via Win128) regarding:
 Type ("trigger condition")
 Supervised / Not supervised
 Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or Normally closed (low resistance, 680R, when supervised)
 Additional information depending on selected type
10
In this case: Relay normally not activated / Relay normally activated.
11
Relay contact ratings (COM / NO / NC): max. 2 A @ 30 V DC.
12
A control expression is also required, i.e. Fire Brigade Tx.
Regarding "Fire brigade tx", see also chapters "Alert Annunciation", page 92
and "Fire alarm type A and Fire alarm type B", page 96.
13
It is possible to use a programmable input with trigger condition Activated
routing equipment, to turn on the LED instead.
14
Also if EBL128 becomes powerless (dead) and for "Watch-dog fault".
EBL128 Planning Instructions V1.1.x
12
Activated output is indicated
13
This output can be disabled via "door
11
This output for routing equipment
14
. De-activated output is also
19