I/O Matrix Board 4582 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
5.5
COM loop
Application
boards:
Input 0 (J1:3-4):
Fire alarm routing equipment fault (Melder
quittung)
Input 1 (J1:7-8): German key cabinet (FSK rückmeldung)
Input 2 (J1:9-10): German key cabinet (FSK überwachung)
Input 3 (J1:13-14):
ausgelöst)
Input 4 (J1:15-16):
quittung)
See also Win128 help or chapter "Programmable inputs", page 54.

I/O Matrix board 4582

A special type of expansion board that can only be used together with
an Application board (Fan, Generic or Zone).
The I/O Matrix board makes it possible for any retailer to manufacture
and connect three different types of "Application boards" to EBL128
via the COM loop.
EBL512
NOTE!
C.i.e.
Up to 16 I/O Matrix board 4582 per EBL512 C.i.e.
Up to 4 (No. 0-3) I/O Matrix board 4582 per COM loop.
Up to 4 I/O Matrix boards type Generic and/or Zone per EBL512 C.i.e.
24 V DC
Type:
Fan
I/O
Matrix
Fan c.i.p. board
board
4582
No. 0
Fan c.i.p.
Mimic panel / New Zealand i.p.
Figure 6. I/O Matrix board application overview. The COM
loop and 24 V DC are internally connected to the I/O Matrix
board.
The I/O Matrix board (80 x 63 mm) is plugged ("piggy back"
connection) to the Application board respectively and has 16 inputs
and 48 outputs.
The COM loop and 24 V DC is connected to
Application board.
Three different application board types can be selected via jumpers
(JP4-JP5) on the I/O Matrix board:
Generic control and indicating panel (Mimic panel alt. New Zealand
indication panel), with 16 inputs (any input trigger condition can be
used) and 48 outputs (any output trigger condition can be used).
Fan control and indicating panel, for four Fan control panels, each
with six LED:s (On / Auto / Off / Running / Stopped / Fault) and three
push buttons (On / Auto / Off). One "Reset" switch. Can be used for
a "Supply air fan" or a "Standard fan".
Zone control and indicating panel, with outputs and inputs for 16 zone
LED:s (Alarm / Fault / Disabled) and 16 push buttons (Disable).
There is no COM loop address to be set. Instead, the expansion
EBL128 Planning Instructions V1.1.x
German extinguishing system (Löschanlage
German extinguishing system (Löschanlage
21
Generic
I/O
Matrix
Generic
board
c.i.p. board
4582
No. 1
27
Zone
I/O
Matrix
Zone c.i.p. board
board
4582
No. 3
Zone c.i.p.