Panasonic EBL128 Planning Instructions page 35

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.1.1.2
6.1.1.3
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
Addressable Manual Call Points
3333 Addressable Manual Call Point.
built-in LED will indicate that fire alarm is generated, i.e. the
glass is broken.
supplied test key without breaking the glass.
polycarbonate flap is protecting the glass.
address is set with an Address setting tool (AST) 3314. The
call point has an address label on which the programmed
technical address is to be written.
3333 is to be surface mounted in the supplied red backbox or
flush mounted in a Swedish 65mm circular mounting box. For
indoor use and in dry premises.
The Address setting tool 3314 is also used for mode setting.
NORMAL mode: Flashing or not flashing LED (see Product
leaflet MEW00097) is set via Win128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
3339 Enclosed Addressable Manual Call Point.
but another type of front cover and backbox.
mounting. For indoor use in premises where IP67 rating is
required.
Analog Detectors
3308 Analog heat detector. To be plugged in an ASB base 3312.
Built-in LED that is lit to indicate that the detector has
generated fire alarm.
attached). The technical address is set with an Address setting
tool (AST) 3314. The detector has an address label on which
the programmed technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: 3308 is in this mode via Win128 set to one
of three algorithms (static response temp. range) for class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
3309 Analog heat detector. Enclosed (IP67)
lit to indicate that the detector has generated fire alarm.
33
In all conventions the manual call points have a response time < 5 s.
34
As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 70°C), -20°C < T
EBL128 Planning Instructions V1.1.x
33
Conforms to EN54-11. A
Routine testing can be performed with a
Prepared for mechanical lock (screw
34
. Built-in LED that is
< 65°C.
a
33
A hinged
The technical
33
Like the 3333 unit