10.5.1

Control expression

Each programmable output has to be given a control expression (with
one or more trigger conditions), made by so called Boolean algebra.
Trigger conditions (displayed a list by clicking the right mouse
button), logical "Operators" (AND, OR, NOT) and parentheses are
used to build up a "control expression" containing up to 40 trigger
conditions. See also chapter "Control expression examples" page 72
and the Win128 help.

Trigger conditions

Some trigger conditions require additional information, see
parentheses (+nnnnn) after the trigger condition respectively.
Consecutive trigger conditions includes a "Quantity" that shows the
number of alarm points within the sequence that have to be activated
to fulfil the trigger condition. (Quantity = 1-10. "1" is normal.)
The following trigger conditions are available:
1
Fire Alarm Zone (+Zone no.)
2
Fire Alarm Zone Address (+Zone no.+Address)
3
General Fire Alarm
4
Consecutive Fire Alarm (sequence) (+start Zone no. and
address +stop Zone no. and address +Quantity)
5
Pre Warning Zone (+Zone no.)
6
Pre Warning Zone Address (+Zone no.+Address)
7
General Pre Warning
8
Consecutive Pre Warning (+start Zone no. and address
+stop Zone no. and address +Quantity)
9
Heavy Smoke Alarm Zone (+Zone no.)
10
Heavy
Smoke
no.+Address)
11
General Heavy Smoke Alarm
12
Consecutive Heavy Smoke Alarm (sequence) (+start
Zone no. and address +stop Zone no. and address
+Quantity)
13
Two Address Dependent Fire Alarm (+Zone no.
+Address)
14
Interlocking Input Area Activated (+Area no.)
15
Interlocking Input Area Point Activated (+Area no.
+Point)
16
General Interlocking Input Activated
17
Consecutive Interlocking Input Activated (sequence)
(+start Area no. and point +stop Area no. and point
+Quantity)
18
Indication Fire Brigade Tx Activated
19
Indication Fault Tx Activated
20
Fire Brigade Tx Disabled
21
Zone Disabled (+Zone no.)
22
Zone Address Disabled (+Zone no. +Address)
EBL128 Planning Instructions V1.1.x
Alarm
Zone
68