Re-Enable Interlocking Output (C5) - Panasonic EBL128 User Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
10.5

Re-enable interlocking output (C5)

Not available for users with access level / type "Information only".
Disabled interlocking outputs are listed in menu H4/U1.
Individually disabled interlocking outputs (Type = Interlocking) have
to be re-enabled via this menu (C5).
All interlocking outputs disabled via menu H2/B4, has to be re-
enabled via menu H2/B8.
If there are no interlocking outputs to re-enable,
--- List is empty --- will be shown.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "9") to menu H9.
H9 Interlocking outputs and inputs
Press "A" to sub menu C1.
C1 Activated interlocking outputs / inputs
Scroll (or press "5") to menu C5.
C5 Re-enable interlocking output
Press "A". This is a list in which you can scroll. Select the Area –
Point for the interlocking output to be re-enabled. Press "A" to re-
enable the output or press "Return" (P9) to menu C5.
Press "A". If more interlocking outputs shall be re-enabled do as
above, if not press "Return" to menu C5.
Scroll to another menu or press "Return" to menu H9. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual
35