Mitsubishi Electric AE-200A/AE-50A Instruction Book page 44

Air conditioning control system
Table of Contents

Advertisement

(4) Setting the contents of the schedule
Click [Edit] in the Contents of Schedule section to display the schedule settings screen.
Scheduled start time
Schedule settings
OK
Set the start time to apply to the schedule, set the operations to be scheduled, and then press [OK].
The operations that can be scheduled for air conditioning unit groups are as follows: ON/OFF/Optimized Start,
Mode, Set Temp, Air Direction, Fan Speed, and Prohibit Remote Controller Operation.
Up to 24 events can be scheduled per day.
Note: The operation items that will appear on the screen vary, depending on the group type.
Note: [Optimized Start] can be selected only for the air conditioning unit groups.
Note: If [Optimized Start] is selected, the operation mode and the set temperature need to be set as well. The Optimized Start
function will start the units 5 to 60 minutes prior to the scheduled start time to reach the set temperature at the scheduled
start time, based on the operation data in the past. (When the units start the first time after a power reset, the units will
start operation 30 minutes before the scheduled start time.)
If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the measured
value may not be an accurate representation of the temperature in the room, especially when the air conditioning unit
is stopped and the room air is stagnant. When this is the case, use an external temperature sensor (PAC-SE40TSA) or
remote controller sensor to measure the room temperature.
Note: If [Optimized Start] is selected and the [Prohibit Remote Controller Operation] setting is set to Prohibit or Permit at the
same time, the operations from the remote controllers will be prohibited or permitted at the scheduled start time.
Note: When setting a schedule for a block or all groups, all operation modes are available for selection, but the available
operation modes depend on the unit model. The units will not operate in the selected mode not supported by the units.
Note: For LOSSNAY unit groups, the item [Set Temp.] or [Air Direction] will not appear, and only ON/OFF setting under the
Prohibit Remote Controller Operation can be made.
Note: For general equipment groups, only the operation ON/OFF settings can be made.
WT07139X01
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae-200e/ae-50e

Table of Contents