Hitachi PC-ARFG-E Installation & Operation Manual page 54

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
Element
Optional function
J2
Not used
J3
Colour of the run indicator
Override of Start/Stop
J4
prohibition at the remote
controller
J5
Not used
J6
Error Sound
J7
Not used
J8
Eco-operation
(7)
J9
Not used
Display of "Simple
JA
maintenance display" menu
Jb
Not used
49
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
00
-
-
01
00
Green (factory setting)
X
01
Red
00
Start/Stop allowed (Factory setting)
Start/Stop not allowed
!
X
01
Blocking of Start/Stop shall never be
set due to safety concerns.
02
Only Stop allowed
00
-
-
01
00
Once
X
01
Continuous
00
-
01
Function disabled
00
(factory setting)
X
01
Function enabled
00
-
-
01
Function disabled
00
(factory setting)
O
01
Function enabled
00
-
01
Setting conditions
D A N G E R
Description
Use at 00 conditions
When there is a remote control
prohibition from a central control
device, this function overrides
this prohibition allowing the
operation of the Run/Stop button
of the remote control switch.
Models:
RPF(I)-FSN2E
Not used. Use at 00 conditions
Use at 00 conditions
To produce a sound when unit is
on alarm.
Use at 00 conditions
When the unit is restarted by
the remote control switch, the
temperature automatically
changes to the setting
temperature of "F5" or "F6".
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
Use at 00 conditions
Enables the "Simple
maintenance display" menu.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
Use at 00 conditions