Hitachi PC-ARFG-E Installation & Operation Manual page 45

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU

Table A. Optional Setting Items for Function Selection
Element
Optional function
Heating temperature
compensation
Models:
All indoor units except
RPF(I)-FSN2E
b1
Heating temperature
compensation
Models:
RPF(I)-FSN2E
Circulation function at heating
b2
Thermo-OFF
b3
Not used
Change of filter cleaning
b4
period
Locking of operation mode
b5
(Not available for models
KPI-E4)
Locking of temperature
b6
setting
Setting operation mode as
cooling only
b7
(Not available for models
KPI-E4)
Automatic COOL/HEAT
operation
b8
(Not available for models
KPI-E4)
40
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
Normal (factory setting)
00
(Setting Temperature + 4ºC)
No compensation
01
(Setting Temperature)
O
02
Setting Temperature + 2ºC
03
Setting Temperature + 3ºC
04
Setting Temperature + 1ºC
RPF(I)-FSN2E: Normal
00
(factory setting)
(Setting Temperature + 2ºC)
No compensation
O
01
(Setting Temperature)
02
Setting Temperature + 2ºC
Function disabled
00
(factory setting)
O
01
Function enabled
00
-
01
00
Standard (1200 hours)
01
100 hours
1200 hours
O
02
(factory setting)
03
2500 hours
04
No indication
Function disabled
00
(factory setting)
X
01
Function enabled
Function disabled
00
(factory setting)
X
01
Function enabled
Function disabled
00
(factory setting)
X
01
Function enabled
00
Function disabled (factory setting)
X
01
Function enabled
Setting conditions
Description
This function is used to adjust
the temperature difference
between the temperature read
by the inlet sensor and the real
room temperature.
This is useful when the inlet air
thermistor is not placed inside
the indoor unit or due to uneven
heat load.
Note:
The "02", "03", "04" settings
may not be available
depending on the type of
indoor unit.
This setting shall be
performed separately for
each indoor unit, even in
case that multiple indoor
units are connected to one
remote controller.
This function keeps the fan
running during the Thermo-OFF
sequence, at the fan speed set
on the remote control switch, to
prevent the stratification of air in
the room.
Use at 00 conditions
This function is used to modify
the period of operation after
which the air filter cleaning
indication is shown in the remote
control.
For RPK-FSR(H)M models,
the factory setting is b4=00:
Standard setting 200 hours.
This function prevents the
modification of the operation
mode of the unit from the remote
controller and from central
controls, once it has been
selected.
This function prevents the
modification of the setting
temperature of the unit from
the remote controller and from
central controls, once it has
been selected.
This function is used to limit the
operation mode to cooling only
and to prevent heating mode
from being enabled.
This function enables the
selection of Auto cool/heat
operation mode. If the function
is not activated, Auto cool/heat
mode cannot be selected on the
remote control switch.

Advertisement

Table of Contents
loading

Table of Contents