Hitachi PC-ARFG-E Installation & Operation Manual page 51

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
Element
Optional function
Ed
Not used
Control in "Automatic" indoor
EE
fan speed mode
Control in "Automatic" indoor
fan speed mode (supporting
High H)
Models:
RCI-FSR
EF
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3(P)E(-f)
RPK-FSR(H)M
F0
Not available
Automatic OFF timer setting
Models:
RCI-FSR
RPC-FSR
RPK-FSRM
RPI(L/H)-FSRE
RCD-FSR
RCIM-FSRE
RPI-FSN3(P)E(-f)
F1
Automatic OFF timer setting
Models:
RPF(I)-FSN2E
Remote control primary-
F2
secondary setting
46
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
00
O
-
01
Function disabled
00
(factory setting)
O
01
Enabled
00
Function disabled
O
01
Function enabled
"- -" permanent –
Function disabled
00
(Factory setting)
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
0A
30 minutes
X
0B
90 minutes
0C
40 minutes
0D
45 minutes
0E
50 minutes
0F
55 minutes
Function disabled
00
(Factory setting)
01
1 hour
02
2 hours
X
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
Primary (main remote control)
00
(Factory setting)
X
01
Secondary (sub remote control)
Setting conditions
}
Do not set these
when two wired
controllers are used.
Description
Use at 00 conditions
This function limits the speed
of the indoor fan when room
temperature is close to the
setting temperature.
This function limits the speed
of the indoor fan when room
temperature is close to the
setting temperature, allowing to
reach High H speed.
This function sets an automatic
OFF timer to switch OFF the
indoor units controlled by the
remote control switch (when
the units have been started by
remote control).
(Do not set the values "0C"-
"0F" when two remote control
switches are used in the same
remote control group).
This function is used to set the
automatic timer to switch off
when the unit has been started
by remote control.
This function is used to define
which remote control switch is
used as primary or secondary,
when two remote controllers are
connected to one indoor unit.

Advertisement

Table of Contents
loading

Table of Contents