ABB Ekip Touch Operating Instructions Manual page 8

Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
8
Step 5. Press the upper left icon - Protections Icon
A DJ U S T I N G T H E L O N G T I M E P R O T E C T I O N S E T T I N G S
Factory Default Settings
Protection Function
Long Time Protection
L Protection Overload (49)
Range Adjustability
Protection Function
Long Time Protection
L Protection Overload (49)
Step 6. Press the L Protection Overload (49) row
Frame
Enabled
Trip Enabled
XT5
XT7/XT7M
ON
-
Emax 2
Frame
XT5
XT7/XT7M
Emax 2
Function /
Threshold /
Time /
Curve
Pickup
Delay
t1 = 48 seconds
t = k/I2
I1= 1 x In
t1 = 144 seconds
t1 = 144 seconds
Threshold / Pickup Range
0.4 x In to 1 x In; in 0.001 In steps
5
Thermal
Pre-alarm
Memory
OFF
90% I1
Time / Delay Range
3 - 48s in 1s steps
3 - 144s in 1s steps
3 - 144s in 1s steps
6