In the event of an alarm, it commands a TRIP Ekip Touch Trip unit for SACE Tmax XT5 CB, equipped with touchscreen display and available in six different versions Trip coil CB opening actuator controlled directly by Trip unit...
ABB | SACE Tmax XT Introduction 1 - Contents Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Tmax XT5 CB, among which: general overview: management operations: putting into service, maintenance, troubleshooting operating conditions...
• anyone who is implementing procedures or using maintenance devices recommended by ABB or not must check carefully that neither their personal safety nor the safety devices are endangered by the installation, operation, maintenance method or by the tools used; contact your nearest ABB representative for further information, explanations or specific problems •...
ABB | SACE Tmax XT Overview of Ekip Touch 1 - General characteristics Families SACE Tmax XT5 can be configured to operate with two Trip unit families: • Ekip Dip with interface via dip-switches • Ekip Touch with touchscreen display Both families provide protection and measuring functions related to signals from the installation and are available in different models and versions.
Page 16
• UniSec, for configuring medium voltage switchgear Front CAD Software comprising libraries of block graphics for ABB panel-making products to be used with the latest versions of AutoCAD, AutoCAD LT, IntelliCAD NOTE: the link launches the software package download, which requires about 190 Mb of space.
Reset Wizard command: in this case, Wizard will appear when the apparatus is powered up the next time. NOTE: for security reasons, ABB strongly advises you to change the PIN right from the first access and to keep it in a safe place...
Page 23
NOTE: check error messages on display before consulting the table; if the suggestions given fail to resolve the problem, call the ABB assistance service and provide the report produced by the Ekip Connect software if possible...
Disabling The PIN code can be disabled by entering its value as: 00000; In this case, the PIN is only required to change the PIN itself in the Settings menu. Recovery if the PIN code is lost, consult document 1SDH001501r0002, available in the ABB website, or contact ABB directly.
• the device nearest to the fault trips • the other devices are blocked for a programmable time NOTE: connection can be made between ABB devices that have the zone selectivity function Characteristics Ekip Touch has five selectivity connections, located on the rear connectors of the CB:...
Page 75
• The other devices are blocked for a programmable time NOTES: • connection can be made between ABB devices that have the zone selectivity function • disable the zone selectivities of protections S, S2 and G to correctly use the selectivity D function...
Page 117
BLE - Connection security Activation of LV communication requires the Trip unit to be pre-engineered for a wireless connection: security of the data and LV connection between the Trip unit and its device is guaranteed thanks to the ABB Ekip Connect Mobile application and the pairing configuration.
• models up to 250A at 400A can be installed if the original Rating Plug is 400A or less • models up to 250A at 630A can be installed if the original Rating Plug is 500A or 630A Further details about assembly and the Rating Plug installation procedure are available in ABB Library, particularly in document 1SDH002011A1505.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
Ekip Supply module on the basis of the customer's own application and network. For applications in low voltage installations ABB suggests use of the dedicated isolated external sensor PT1000, which can be ordered by code 1SDA085695R1,...
Each Ekip Link can interface with up to 15 actors, of which up to 12 can be for the Zone Selectivity function. The ports used by the module are: Port Service Notes 18/UDP ABB proprietary In the case of rapid exchanges of information among ABB devices 319/UDP IEEE 1588 Valid with IEEE 1588 protocol enabled 320/UDP 68/UDP...
The inputs and outputs can be fully configured by the user The module can be supplied by 110...240 V AC / DC or 24...48 V DC. Further details about Ekip Signalling Modbus TCP are available in ABB Library, especially in document 1SDH001456r0002.
(V0). To configure the presence of the sensor and protection, please consult pages 33 and 47. Further details about the External neutral connection are available in ABB Library, especially in document 1SDH001000r0506.
The communication protocol used is Bluetooth Low Energy (Bluetooth 4.1). Ekip Bluetooth Key is compatible with all the trip units installed in ABB Tmax XT and Emax 2 low voltage circuit-breakers. Further details are available in ABB Library, especially in document 1SDH002023A1001.