Protection settings setup for touch trip units

Advertisement

E K I P T O U C H T R I P U N I T S
28
A DJ U S T I N G T H E L O N G T I M E P R O T E C T I O N S E T T I N G S
Factory Default Settings
Protection Function
Long Time Protection
L Protection Overload (49)
Range Adjustability
Protection Function
Long Time Protection
L Protection Overload (49)
Step 5. Press the Enter button (5) on L Protection row
Step 6. Press Down button (6a) to Threshold I1 and then Enter button (6b)
Step 7. This display is presented (In order to change settings, a password is required)
Default password: 00001. Zero appears in the first PIN box.
Press Enter button (7a) to accept zero
Repeat for the next three PIN boxes
On the 5th PIN box change from zero to one (press the Up button (7b)), then press Enter button (7a)
This will allow Protection Settings to be changed per the coordination study
Note: Once the PIN code has been entered, all displays can be browsed for two minutes: once two minutes has elapsed, the PIN code must be entered
again (depending on the case in question).
Frame
Enabled
Trip Enabled
XT2 & XT4
ON
-
Frame
Threshold /Pickup Range
XT2 & XT4
0.4 x In to 1 x In; in 0.001 In steps
Function /
Threshold /
Time /
Curve
Pickup
Delay
t = k/I2
I1= 1 x In
t1 = 12 seconds
6a
6b
Thermal
Pre-alarm
Memory
OFF
90% I1
Time /Delay Range
3 - 60 s in 1s steps
5
7a
7b