P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
11
Step 11.
The setting range is from 3 to 144 Seconds (3 to 48 seconds for XT5)
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given in seconds and can be set within the range: 3 seconds to 144 seconds, in 1 second steps.
Step 12. Press the left arrow key
12
This completes the settings of the Long Time / L Protection Function.