E K I P T O U C H T R I P U N I T S
34
A DJ U S T I N G T H E S H O R T T I M E D E L AY O R T I M E T 2
Step 19. Press the Down button (19a) to select Time t2 and then press the Enter button (19b)
Step 20. Change the Short Time Delay / Time t2 setting to the value in the coordination study using the Up
and Down buttons (20a) and Press the Enter button (20b).
The setting range is from 0.05 to 0.8 Seconds (UL Version: t4 Max = 0.4s)
Press Up or Down buttons (20a) to change to the value in the coordination study. Then press Enter button
(20b).
Holding the Up or Down (20a) buttons will advance the settings faster.
NOTE: The value is given in seconds and can be set within the range: 0.05 seconds to 0.8 seconds, in 0.01 second steps.
Step 21. Press ESC button (21)
This completes the settings of the Short Time / S Protection Function.
19a 19b
20a 20b
21