P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
A DJ U S T I N G T H E S H O R T T I M E P R O T E C T I O N S E T T I N G S
Factory Default Settings
Protection Function
Short Time Protection
S Protection Selective Short Circuit (51/50TD)
*Protection must be Enabled=ON to input the settings.
Range Adjustability
Protection Function
Short Time Protection
S Protection Selective Short Circuit (51/50TD)
Step 12. Press Down button (12a) to select S Protection and Press Enter button (12b)
Step 13. Press Enter button (13) on Enable
Step 14. Press Down button (14a) to On and press Enter button (14b)
Trip
Function /
Frame
Enabled
Enabled
Curve
XT2 & XT4
OFF*
ON
t = k
Frame
Threshold /Pickup Range
XT2 & XT4
0.6 x In to 10 x In; in 0.1 In steps
12a 12b
14a 14b
Threshold /
Time /
Thermal
Pickup
Delay
Memory
I2 = 2 x In
t2 = 0.1 seconds
-
Time /Delay Range
0.6 x In to 10 x In; in 0.1 In steps
31
Pre-
alarm
-
13