11 Configuration Parameters in Flame Explorer
Frequency
Frequency option outputs the Flicker-Frequency value which is proportional to the
maximum Flicker-Frequency for the application selected.
For corner applications: 4 to 20 ma = 0 - 125 Hz
For wall/industrial applications: 4 to 20 ma = 0 - 125 Hz
For lighter applications: 4 to 20 ma = 0 - 125 Hz
For gas turbines or pyrometer: 4 to 20 ma = 0 -125 Hz or 0 - 250 Hz
AC-Amplitude
This option will output the AC-Amplitude in a range of 4 to 20 mA = 0 to 100%.
Quality (default)
This option will output the quality value in a range of 4 to 20 mA = 0 to 100%.
Core Temperature
Core temperature ranges from -60 to 110 Celsius degree. It is scaled from 0 to 100%.
This option will output the core temperature value in a range of 4 to 20 mA = 0 to 100%.
Flame Temperature
Flame temperature ranges from 800 to 1800 Celsius degree. It is scaled from 0 to 100%.
This option, that is available only if the used sensor type is pyrometer, and will output
the flame temperature value in a range of 4 to 20 mA = 0 to 100%.
Quality Combination
This option is valid for dual sensor only. It uses higher quality value, if the alternative
flame logic "OR", and lower quality value, if alternative flame logic is "AND".
This option will output the quality value in a range of 4 to 20 mA = 0 to 100%.
Load Default Parameters
From the local touch-buttons/display, it is possible to request to the unit to load back its
factory default parameters.
In this way, all the unit parameters will be brought back to the factory default with the
following exception the active protocol will not change:
If the unit is MODBUS, it will remain MODBUS (but will bring back address and baud
rate to 1/38.400).
8VZZ005286 B