2 Hardware
2.2 Display and Terminations Boards
Field site shall provide +24V
acceptable input power supply voltage range: +24V
in
Appendix
to EN 50178 1997 Electronic Equipment in Power Installations.
For SIL2 application, the customer suggest to provide the redundancy power supply,
shall with power voter that will have extra 24V over-voltage protection with threshold
no more than 35VDC, to ensure the maximum power input to SF910i shall not
exceed 35VDC even when power supply enter critical failure mode.
For SIL2 safety, IEC 60730-1, CAN/CSA E60730-1, or EN298 application, Safe-relay
need to be set into "second flame relay" condition, and needs to be serially connected
with Flame-relay contacts by customer to fulfil safety redundancy output.
Despite having inrush current limitation circuits, the inrush current measured when
there is a step application of 24V
few ms (see
distribution circuit breakers or fuses to be used with SF910i. See
the inrush current value.
The internal non-replaceable fuse is intended to protect against internal damage in case
of excess current consumption.
SF910i is protected against polarity inversion of the 24V
Individual protection against overload or short circuit realized on external power distribution
panel shall be suitably rated, with time lag. ABB suggests mounting a dedicated circuit
breaker for each scanner, for instance, a thermal-magnetic circuit breaker, 1A curve "K".
2.2.3

Relays

There are two relays in the SF910i. One is the main flame relay and the other is
configurable with internal parameter, for example:
Second flame relay
Watch dog
Flame quality
Scanner case skin temperature
The relay contacts are galvanic isolated.
summary.
8VZZ005286 B
to SF910i through external power supply modules. Target
DC
A. It shall have CE mark and fulfil the requirement of SELV/PELV according
Appendix
A). Consider this when selecting the appropriate power
, <= +20%, >= -25%, as claimed
DC
peaks to a relatively high value and settles in a
DC
DC
Section 13
reports the relay assignment
Appendix A
power supply.
for
35

Advertisement

Table of Contents
loading

Table of Contents