Technical Specifications

Table A.1: Technical Specifications
Property
Optical spectrum
Optical sensor technology
Power supply voltage
Power supply current
Power consumption
Inrush current
Hot insertion/removal
Flame-relay
Safe-relay
Flame-relay drop-out time
Flame-relay pull-in time
Analog output (4-20mA)
8VZZ005286 B
IR versions: 320 -1100 nm peak sensitivity @ 920 nm
UV versions: 210 - 360 nm peak sensitivity @ 280 nm
UVIR versions: Combination of above IR and UV sensitivities
PYR: Dual colors IR
IR versions: Si photodiode
UV versions: SiC photodiode
UVIR versions: One Si and one SiC photodiodes
PYR: Si Photodiode
24V
(-25%, +20% = 18 - 29V
DC
150mA typical
3.6W typical and 4W maximum
6A peak and 2ms settling time
Allowed
Contacts: 1 NO, for each relay
50 V
/1.5A cycles 100,000
AC
48 V
/300 mA
DC
30 V
/1.5A
DC
Minimum load 10mA, 5V
0.2s to 4.0s at 0.1s increments (configurable setting)
2s default
0.2s to 10s at 0.1s increments (configurable setting)
2s default
4 - 20 mA (R load <= 500)
Galvanically isolated
Value
)
DC
DC
131