USER MANUAL AND SPECIFICATIONS NI cRIO-9023 Intelligent Real-Time Embedded Controller for CompactRIO This document describes how to set up and use the NI cRIO-9023 and contains specifications for the controller. Figure 1. cRIO-9023 Front Panel 1. LEDs 6. Reset Button 2.
II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the cRIO-9023 in Gas Group IIC hazardous locations, you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Installing the cRIO-9023 on the Chassis Complete the following steps to install the cRIO-9023 on the chassis. Make sure that no power is connected to the cRIO-9023 or the chassis. Align the cRIO-9023 with the chassis as shown in the following figure.
Page 5
2. Captive Screws 4. Chassis Slide the cRIO-9023 onto the chassis connector. Press firmly to ensure the chassis connector and the cRIO-9023 connector are mated. Using a Phillips #2 screwdriver, tighten the two captive screws on the front of the cRIO-9023 to 1.3 N ·...
Page 6
1. M4 Thread Connecting the cRIO-9023 to a Network Connect Ethernet port 1 on the cRIO-9023 to an Ethernet network using a standard Category 5 (CAT-5) or better Ethernet cable. The host computer communicates with the controller over a standard Ethernet connection. If neither the host computer nor the controller is connected to a network, you can connect the two directly.
You must install the cRIO-9023 on a chassis or use stand-alone mounting Caution kit such as the NI 9908 or NI 9909 before wiring power to the cRIO-9023. Installing the cRIO-9023 while power is connected can damage the chassis. The cRIO-9023 requires a 35 VDC external power supply. The cRIO-9023 filters and regulates the supplied power and provides power for the C Series modules.
Page 8
Power on the primary power supply and optional secondary power supply. Powering On the cRIO-9023 When you power on the cRIO-9023 for the first time, the device runs a power-on self test (POST). During the POST, the Power and Status LEDs turn on. When the Status LED turns off, the POST is complete.
Ethernet port 2. RS-232 Serial Port The cRIO-9023 has an RS-232 serial port to which you can connect devices such as displays or input devices. Use the Serial VIs to read from and write to the serial port. For more information about the Serial VIs, refer to the LabVIEW Help.
You can connect multiple USB mass-storage devices to the cRIO-9023 if you use a USB hub. Refer to the LabVIEW Help for more information. If the cRIO-9023 is not in a hazardous location, you can connect and Note disconnect USB devices without affecting operation.
Description Essential services required for updating its configuration and installing software launch when the cRIO-9023 boots. Place this switch in the ON position if the software on the controller is corrupted or reformat the drive on the cRIO-9023. The embedded LabVIEW Real-Time engine launches when the cRIO-9023 boots.
Description Restore the cRIO-9023 to the default network settings. Reboot the cRIO-9023 to reset the IP address and other TCP/IP settings of the cRIO-9023 to the factory defaults. Keep this switch in the OFF position during normal operation. NO APP Switch The following table describes the ON and OFF states of the NO APP switch.
Measurement & Automation Explorer (MAX) Help for information about installing software on the cRIO-9023. Blinks three times and The cRIO-9023 is in a user-directed safe mode. Use the SAFE pauses MODE DIP switch to turn off safe mode. Blinks four times and The cRIO-9023 is in safe mode.
Page 14
Resetting the Network Configuration of the Controller If the cRIO-9023 cannot communicate with the network, you can use the IP RESET switch to manually restore the default network settings. Complete the following steps to restore the cRIO-9023 to the default network settings.
256 MB For information about the life span of the nonvolatile memory and about best Note practices for using nonvolatile memory, go to and enter the Info ni.com/info Code SSDBP 14 | ni.com | NI cRIO-9023 User Manual and Specifications...
9 V to 35 V After powerup 6 V to 35 V The cRIO-9023 is guaranteed to power up when 9 V is applied to V and C. Note After powerup, it can operate on as little as 6 V.
To meet these specifications for shock and vibration, you must panel mount or wall mount the cRIO-9023 system, affix ferrules to the ends of all terminal wires, install a strain relief on the power cable, and install tie wraps on the Ethernet and power cables. You can order the NI 9979 strain-relief kit for the power cable.
National Instruments 符合中国电子信息产品中限制使用某些有害物 中国客户 质指令(RoHS)。关于 National Instruments 中国 RoHS 合规性信息,请登录 。(For information about China RoHS ni.com/environment/rohs_china compliance, go to ni.com/environment/rohs_china Ethernet Cabling The following table shows the standard Ethernet cable wiring connections. 18 | ni.com | NI cRIO-9023 User Manual and Specifications...