Fuses; Ul Class T And L Fuses - ABB ACS800-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

116 Technical data

Fuses

UL class T or L fuses for branch circuit protection per NEC are listed below. Fast
acting class T or faster fuses are recommended in the USA.
Check from the fuse time-current curve that the operating time of the fuse is below
0.1 seconds. The operating time depends on the supply network impedance and the
cross-sectional area and length of the supply cable. The short-circuit current can be
calculated as shown on page 103.

UL class T and L fuses

ACS800-U4
type
current
Three-phase supply voltage 208 V, 220 V, 230 V, 240 V
-0080-2
-0100-2
-0120-2
-0140-2
-0170-2
-0210-2
-0230-2
-0260-2
-0300-2
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0170-5
-0210-5
-0260-5
-0270-5
-0300-5
-0320-5
-0400-5
-0440-5
-0490-5
-0550-5
-0610-5
Three-phase supply voltage 525 V, 575 V or 600 V
-0140-7
-0170-7
-0210-7
-0260-7
Input
A
A
201
250
239
300
285
400
391
500
428
600
506
600
599
800
677
800
707
900
175
250
220
300
267
400
293
500
331
500
397
500
467
600
501
800
542
800
614
900
661
900
117
200
146
200
184
250
199
300
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Ferraz
600
Ferraz
600
Ferraz
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Ferraz
600
Ferraz
600
Ferraz
600
Ferraz
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
Type
UL class
JJS-250
T
JJS-300
T
JJS-400
T
JJS-500
T
JJS-600
T
JJS-600
T
A4BY800
L
A4BY800
L
A4BY900
L
JJS-250
T
JJS-300
T
JJS-400
T
JJS-500
T
JJS-500
T
JJS-500
T
JJS-600
T
A4BY800
L
A4BY800
L
A4BY900
L
A4BY900
L
JJS-200
T
JJS-200
T
JJS-250
T
JJS-300
T

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04mAcs800-u4

Table of Contents