Non-ABB high-output and IP23motors
Note 4:
The rated output power of high output motors is higher than what is stated for the
particular frame size in EN 50347:2001. The table below shows the requirements for
random-wound and form-wound non-ABB motors with nominal power smaller than
350 kW. For bigger motors, consult the motor manufacturer.
Nominal AC
supply voltage
Motor insulation
U
< 420 V
Standard:
N
1300 V
U
420 V <
< 500 V Standard:
N
1300 V
or
Reinforced:
1600 V,
0.2 microsecond
rise time
U
500 V <
< 600 V Reinforced:
N
1600 V
or
Reinforced:
1800 V
U
600 V <
< 690 V Reinforced:
N
1800 V
Reinforced:
2000 V,
0.3 microsecond
rise time ***
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor
braking, check with the motor manufacturer if additional output filters are needed in the applied
drive operation range.
HXR and AMA motors
Note 5:
All AMA machines (manufactured in Helsinki) for drive systems have form-wound
windings. All HXR machines manufactured in Helsinki starting 1.1.1998 have form-
wound windings.
ABB motors of types other than M2_, M3_, HX_ and AM_
Note 6:
Use the selection criteria given for non-ABB motors.
u
ABB d
system
P
< 100 kW or frame
N
size < IEC 315
P
< 134 hp or frame
N
size < NEMA 500
Û
=
+ N or CMF
LL
Û
u
t
=
+ d
/d
LL
Û
=
+ N or CMF
LL
Û
u
t
=
+ d
/d
LL
Û
=
+ N or CMF
LL
Û
u
=
+ N + d
LL
Û
=
N + CMF
LL
Planning the electrical installation 43
Requirement for
t
/d
filter, insulated N-end bearing and ABB common
mode filter
IEC 315 < frame size < IEC 400
NEMA 500 < frame size < NEMA 580
+ N + CMF
+ (N or CMF)
+ N + d
+ N + CMF
u
+ (N or CMF)
+ d
/d
+ N + CMF
t
/d
+ N + d
N + CMF
P
100 kW <
< 350 kW or
N
P
134 hp <
< 469 hp or
N
u
t
/d
+ CMF
t
+ N + CMF
u
t
/d
+ CMF