Fuse tables
ACS800-
Input
04 size
current
A
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2
201
-0100-2
239
-0120-2
285
-0140-2
391
-0170-2
428
-0210-2
506
-0230-2
599
-0260-2
677
-0300-2
707
Three-phase supply voltage 380 V, 400 V or 415 V
-0140-3
196
-0170-3
237
-0210-3
286
-0260-3
438
-0320-3
501
-0400-3
581
-0440-3
674
-0490-3
705
gG fuses
Min.
short-
circuit
current
1)
A
A
A
3820
250
550 000
4510
315
1 100 000
4510
315
1 100 000
8280
500
2 900 000
8280
500
2 900 000
10200
630
4 000 000
10200
630
4 000 000
13500
800
7 400 000
13500
800
7 400 000
3820
250
550 000
4510
315
1 100 000
4510
315
1 100 000
8280
500
2 900 000
10200
630
4 000 000
10200
630
4 000 000
13500
800
7 400 000
13500
800
7 400 000
Fuse
V
Manufacturer
2
s
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
Technical data 105
Type
IEC
size
OFAF1H250
1
OFAF2H315
2
OFAF2H315
2
OFAF3H500
3
OFAF3H500
3
OFAF3H630
3
OFAF3H630
3
OFAF3H800
3
OFAF3H800
3
OFAF1H250
1
OFAF2H315
2
OFAF2H315
2
OFAF3H500
3
OFAF3H630
3
OFAF3H630
3
OFAF3H800
3
OFAF3H800
3