EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

33.1. DURING THE TEST

Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled (also the parts of
the zones in test mode, not visible for the test personnel, are disabled). In order to shorten the testing time, any time delay for the
detectors / zones in test mode will be "disabled", i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up approx. 10 seconds and then the alarm point will be automatically reset. There will be
a test mode alarm indication in the c.i.e. display. The printer, if available, will print out every tested alarm point (Zone: xxx Address:
xx Time: HH.MM).
A detector in test mode is not able to generate a fault.
During the test, the following information will be shown in all other c.i.e. displays:
Zone 001 in test mode
Zone 002 in test mode
...and so on.
When the "Fire door closing" function is used, the fire door will be closed also when the detectors con-
trolling the door are tested in test mode.
33.2.

AFTER THE TEST

The zone(s) will stay in test mode until the test mode is ended. The test mode is ended in menu H7 or automatically one hour after
the latest test alarm. This is valid for each zone respectively.
You will be automatically logged out 15 minutes after the latest "action" (using of any key) but the zone(s) will stay in test mode until
the test mode is ended, see above.
If an alarm point (for example a manual call point) is in alarm state when the test mode is ended, there will
be a fire alarm activated.