EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

19.2.2. SINGLE

Each fire alarm (alarm point / zone) has to be reset one by one.
This function is available only if it is set in EBLWin.
Press "Reset" to reset the fire alarm currently shown in the middle of the display with large digits.
The push button has to be pressed for min. 0.5 sec.
Output(s) programmed for that fire alarm (alarm point / zone) will be reset, i.e. de-activated.
If more than one fire alarm is activated (the LEDs "Alarms queued" are lit) the next fire alarm in the queue will be shown in the mid-
dle of the display. It has to be reset the same way as the first one.
When all fire alarms are reset, LEDs "Fire" and "Alarms queued" are turned off. If there are other conditions (e.g. a fault condition)
the corresponding information will be shown (e.g. a fault message), for the priority order see section
on page 18.
ORDER
All outputs (for fire alarm) are reset.
If a key cabinet is installed, the key (to the building) has to be put back into the key cabinet within 5 minutes. If not, a fault will be
generated and a fault message will be shown in the display, see section
19.6. KEY CABINET ALARM RESET
51
5.4. INFORMATION PRIORITY
on page 53.