The zone(s) will stay in test mode until the test mode is ended. The test mode is ended in this menu or automatically one hour after
the latest test alarm. This is valid for each zone respectively.
You will be automatically logged out 15 minutes after the latest "action" (using of any key) but the zone(s) will stay in test mode until
the test mode is ended.
Perform the test as quickly as possible, since the outputs for routing equipment are disabled during the test mode. Also the parts of
the zones in test mode, not visible for the test personnel, are disabled.
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled", i.e. fire alarm will be
detected faster than normally.
In the tested alarm point, the LED will light up approximately 10 seconds and then the alarm point will be automatically reset. There
will be a test mode alarm indication in the c.i.e. display. The printer, if available, will print out every tested alarm point (Zone: xxx
Address: xx Time: HH.MM). A detector in test mode is not able to generate a fault.
During the test, information on which zones are in test mode will be shown in all other c.i.e. displays.
If an alarm point, for example a manual call point, is in alarm state when the test mode is ended, there will
be a fire alarm activated.
When the "Fire door closing" function is used, the fire door will be closed when the detectors controlling
the door are set in test mode.
88