Mitsubishi Electric FR-E720-600 Instruction Manual page 80

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

Adjust the output torque of the motor (current)
NOTE
The amount of current flows in the motor may become large according to the conditions such as the motor
characteristics, load, acceleration/deceleration time, wiring length, etc., resulting in an overcurrent trip (OL (overcurrent
alarm) then E.OC1 (overcurrent trip during acceleration), overload trip (E.THM (motor overload trip), or E.THT (inverter
overload trip).
(When a fault occurs, release the start command, and decrease the Pr. 0 setting 1% by 1% to reset.) (Refer to page 270.)
The Pr. 0, Pr. 46 settings are valid only when V/F control is selected.
When using the inverter dedicated motor (constant torque motor) with the FR-E720-240 and 330, FR-E740-120 and 170, set torque
boost value to 2%.
When Pr. 0 = "3%"(initial value), if Pr. 71 value is changed to the setting for use with a constant-torque motor, the Pr. 0 setting
changes to 2%.
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 3 Base frequency, Pr. 19 Base frequency voltage
Pr. 71 Applied motor
Pr. 178 to Pr. 184 (input terminal function selection)
78
Refer to page 91
Refer to page 111
Refer to page 131