3.3.4 Wiring of the speed command input terminals
Use shielded or twisted shielded cables for wiring. Connect one shield sheath to
the terminal 5. Leave the other shield sheath open.
The following diagram shows the wiring of the terminal 2.
The same wiring also applies to the other terminals.
3.3.5 Wiring of the transistor output terminals
The terminal SE is a common terminal.
Drive unit
RUN
FU
SE
DC24V
When driving a coil load such as a relay coil, always connect the following diode.
Connect the diode with correct polarity. Opposite polarity will cause the drive unit
to fail.
Terminal SE is isolated from terminals SD and 5. Do not connect
NOTICE
them each other.
1
R
R
2
R
R
9
Drive unit
RUN
SE
3-11
Get other manuals https://www.bkmanuals.com
Drive unit
10
2
5
DC24V
Relay