Mitsubishi Electric FR-D720-0.4K Instruction Manual page 216

Hide thumbs Also See for FR-D720-0.4K:
Table of Contents

Advertisement

Special operation and frequency control
(3)
Connection diagram
Sink logic
Pr. 128 = 20
Pr. 182 = 14
Pr. 190 = 15
∗1
The power supply must be selected in accordance with the power specifications of the detector used.
∗2
The used output signal terminal changes depending on the Pr. 190 , Pr. 192, Pr. 197 (output terminal selection) setting.
∗3
The used input signal terminal changes depending on the Pr. 178 to Pr. 182 (input terminal selection) setting.
∗4
The AU signal need not be input.
214
MCCB
Power supply
Forward rotation
Reverse rotation
PID control selection
Setting Potentiometer
(Set point setting)
AC1φ
200/220V 50/60Hz
Inverter
Motor
R/L1
U
V
S/L2
T/L3
W
STF
STR
RH(X14)
*3
SD
Upper limit
(FUP)RUN
*2
10
2
5
SE
Output signal
common
4
*4
(measured value) 4 to 20mA
0
24V
Power
*1
supply
Pump
IM
P
2-wire type
3-wire type
Detector
+
+
+
-
-
(OUT)
(COM)
(24V)