Monitor display and monitor output signal
(3)
Operation panel I/O terminal monitor (Pr. 52)
When Pr. 52 = "55", the I/O terminal status can be monitored on the operation panel.
The I/O terminal monitor is displayed on the third monitor.
The LED is ON when the terminal is ON, and the LED is OFF when the terminal is OFF. The center line of LED is always
ON.
On the I/O terminal monitor (Pr. 52 = "55"), the upper LEDs denote the input terminal status and the lower the output
terminal status.
RM
RH
RL
RUN
ABC
....Specifications differ according to the date assembled. Refer to page 298 to check the SERIAL number.
(4)
Cumulative power monitor and clear (Pr. 170, Pr. 891)
On the cumulative power monitor (Pr. 52 = "25"), the output power monitor value is added up and is updated in 1h
increments.
The operation panel, parameter unit (FR-PU04/FR-PU07) and communication (RS-485 communication) display
increments and display ranges are as indicated below.
Operation Panel ∗1
Range
0 to 99.99kWh
100.0 to 999.9kWh
1000 to 9999kWh
∗1
Power is measured in the range of 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
∗2
Power is measured in the range of 0 to 99999.99kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in 0.1kWh increments.
∗3
In monitoring with communication, cumulative power is displayed in 1kWh increments. And cumulative power 2 is displayed in 0.01kWh. (Refer to page 187
for communication)
The monitor data digit can be shifted to the right by the number of Pr. 891 settings.
For example, if the cumulative power value is 1278.56kWh when Pr. 891 = "2", the operation panel display or parameter
unit (FR-PU04/FR-PU07) display is 12.78 (display in 100kWh increments) and the communication data is 12.
If the maximum value is exceeded at Pr. 891 = "0 to 4", the power is clamped at the maximum value, indicating that a digit
shift is necessary. If the maximum value is exceeded at Pr. 891 = "9999", the power returns to 0 and is recounted.
If the maximum value is exceeded at Pr. 891 = "9999", the power returns to 0 and is recounted.
Writing "0" in Pr. 170 clears the cumulative power monitor.
REMARKS
If "0" is written to Pr. 170 and Pr. 170 is read again, "9999" or "10" is displayed.
132
STF
STR
SO
Parameter Unit ∗2
Unit
Range
0.01kWh
0 to 999.99kWh
0.1kWh
1000.0 to 9999.9kWh
1kWh
10000 to 99999kWh
Input terminal
Center line is always ON
Output terminal
Range
Unit
Pr. 170 = 10
0.01kWh
0.1kWh
0 to 9999kWh
1kWh
- Display example -
When signals STF, RH and
RUN are ON
Hz
A
V
Communication
Unit
Pr. 170 = 9999
1kWh/
0 to 65535kWh
0.01kWh
(initial value)
∗3