ABB RELION 670 Series Product Manual page 69

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Bay control REC670 2.1 IEC
Table 51. Rate-of-change of frequency protection SAPFRC
Function
Operate value, start function
Operate value, restore enable frequency
Definite restore time delay
Definite time delay for frequency gradient trip
Definite reset time delay
Table 52. Frequency accumulation protection FTAQFVR
Function
Operate value, frequency high limit level at
symmetrical three phase voltage
Operatevalue, frequency low limit level at
symmetrical three phase voltage
Operate value, voltage high and low limit
for voltage band limit check
Operate value, current start level
Independent time delay for the continuous
time limit at f
+0.02 Hz to f
set
Independent time delay for the
accumulation time limit at f
f
-0.02 Hz
set
ABB
GUID-E8D0EE7C-D7B8-46C3-9C0D-363FFC75DE93 v4
Range or value
(35.00 – 90.00) Hz
(30.00 – 85.00) Hz
(0.0 – 200.0)% of UBase
(5.0 – 100.0)% of IBase
(0.0 – 6000.0) s
-0.02 Hz
set
(10.0 – 90000.0) s
+0.02 Hz to
set
M14976-1 v10
Range or value
(-10.00-10.00) Hz/s
(45.00-65.00) Hz
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
1MRK 511 361-BEN D
Accuracy
±10.0 mHz/s
±2.0 mHz
±0.2% or ±100 ms whichever is
greater
±0.2% or ±120 ms whichever is
greater
±0.2% or ±250 ms whichever is
greater
Accuracy
±2.0 mHz
±2.0 mHz
±0.5% of U
at U ≤ U
r
r
±0.5% of U at U > U
r
±1.0% of I
or 0.01 A at I≤I
r
r
±0.2% or ±200 ms whichever is greater
±0.2% or ±200 ms whichever is greater
69

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents