Bay control REC670 2.1 IEC
Voltage protection
Table 44. Two step undervoltage protection UV2PTUV
Function
Operate voltage, low and high step
Absolute hysteresis
Internal blocking level, step 1 and step 2
Inverse time characteristics for step 1 and step 2, see
table
146
Definite time delay, step 1 at 1.2 to 0 x U
Definite time delay, step 2 at 1.2 to 0 x U
Minimum operate time, inverse characteristics
Operate time, start at 2 to 0 x U
Reset time, start at 0 to 2 x U
Operate time, start at 1.2 to 0 x U
Reset time, start at 0 to 1.2 x U
Critical impulse time
Impulse margin time
64
set
set
set
set
set
set
M13290-1 v14
Range or value
UBase
(1.0–100.0)% of
UBase
(0.0–50.0)% of
UBase
(1–50)% of
-
(0.00-6000.00) s
(0.000-60.000) s
(0.000–60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 5 ms
Max. = 25 ms
Min. = 15 ms
Max. = 35 ms
5 ms typically at 1.2 to 0 x U
15 ms typically
1MRK 511 361-BEN D
Accuracy
±0.5% of U
r
±0.5% of U
r
±0.5% of U
r
See table
146
±0.2% or ±40ms whichever is
greater
±0.2% or ±40ms whichever is
greater
±0.5% or ±40ms whichever is
greater
-
-
-
-
-