ABB RELION 670 Series Product Manual page 20

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Bay control REC670 2.1 IEC
Table 5. Basic IED functions, continued
IEC 61850 or function
Description
name
RUNTIME
IED Runtime Comp
CAMCONFIG
Central account management configuration
CAMSTATUS
Central account management status
TOOLINF
Tools Information component
SAFEFILECOPY
Safe file copy function
Table 6. Local HMI functions
IEC 61850 or function
ANSI
name
LHMICTRL
LANGUAGE
SCREEN
FNKEYTY1–FNKEYTY5
FNKEYMD1–FNKEYMD5
LEDGEN
OPENCLOSE_LED
GRP1_LED1–
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15
3. Control
Synchrocheck, energizing check, and synchronizing
SESRSYN
The Synchronizing function allows closing of
asynchronous networks at the correct moment including
the breaker closing time, which improves the network
stability.
Synchrocheck, energizing check, and synchronizing
SESRSYN function checks that the voltages on both
sides of the circuit breaker are in synchronism, or with
at least one side dead to ensure that closing can be
done safely.
SESRSYN function includes a built-in voltage selection
scheme for double bus and 1½ breaker or ring busbar
arrangements.
Manual closing as well as automatic reclosing can be
checked by the function and can have different settings.
20
Description
Local HMI signals
Local human machine language
Local HMI Local human machine screen behavior
Parameter setting function for HMI in PCM600
General LED indication part for LHMI
LHMI LEDs for open and close keys
Basic part for CP HW LED indication module
M12480-3 v15
For systems, which are running asynchronous, a
synchronizing function is provided. The main purpose of
the synchronizing function is to provide controlled
closing of circuit breakers when two asynchronous
systems are going to be connected. The synchronizing
function evaluates voltage difference, phase angle
difference, slip frequency and frequency rate of change
before issuing a controlled closing of the circuit breaker.
Breaker closing time is a parameter setting.
Autorecloser SMBRREC
The autorecloser SMBRREC function provides high-
speed and/or delayed auto-reclosing for single or multi-
breaker applications.
Up to five three-phase reclosing attempts can be
included by parameter setting. The first attempt can be
single-, two and/or three phase for single phase or
multi-phase faults respectively.
Multiple autoreclosing functions are provided for multi-
breaker arrangements. A priority circuit allows one
1MRK 511 361-BEN D
M12390-3 v15
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents