Bay control REC670 2.1 IEC
Maximum 72 outputs may be activated
simultaneously with influencing factors
within nominal range. After 6 ms an
additional 24 outputs may be
activated. The activation time for the
96 outputs must not exceed 200 ms. 48
outputs can be activated during 1 s.
Continued activation is possible with
respect to current consumption but
after 5 minutes the temperature rise
will adversely affect the hardware life.
Maximum two relays per
BOM/IOM/SOM should be activated
continuously due to power dissipation.
Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Min load voltage
Test voltage across open
contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
Making capacity at inductive
loadwith L/R > 10 ms
0.2 s
1.0 s
Making capacity at resistive
load
0.2 s
1.0 s
Breaking capacity for AC, cos j
> 0.4
Breaking capacity for DC with
L/R < 40 ms
Maximum capacitive load
Max operations with load
Max operations with no load
Operating time
46
Trip and Signal relays
IOM: 10
250 V AC, DC
24VDC
250 V rms
8 A
10 A
12 A
30 A
10 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
-
1000
10000
< 6 ms
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
Fast signal relays (parallel reed relay)
IOM: 2
250 V DC
-
250 V rms
8 A
10 A
12 A
0.4 A
0.4 A
220–250 V/0.4 A
110–125 V/0.4 A
48–60 V/0.2 A
24–30 V/0.1 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
10 nF
-
-
<= 1 ms
1MRK 511 361-BEN D
M12584-1 v10