Bay control REC670 2.1 IEC
14. Human machine interface
Local HMI
IEC13000239 V2 EN-US
Figure 5.
Local human-machine interface
The LHMI of the IED contains the following elements:
• Graphical display capable of showing a user defined
single line diagram and provide an interface for
controlling switchgear.
• Navigation buttons and five user defined command
buttons to shortcuts in the HMI tree or simple
commands.
• 15 user defined three-color LEDs.
• Communication port for PCM600.
The LHMI is used for setting, monitoring and controlling.
15. Basic IED functions
Time synchronization
The time synchronization function is used to select a
common source of absolute time for the synchronization
of the IED when it is a part of a control and a protection
system. This makes it possible to compare events and
disturbance data between all IEDs within a station
automation system and in between sub-stations.
34

16. Station communication

Communication protocols
AMU0600442 v14
Each IED is provided with a communication interface,
enabling it to connect to one or many substation level
systems or equipment, either on the Substation
Automation (SA) bus or Substation Monitoring (SM) bus.
Available communication protocols are:
• IEC 61850-8-1 communication protocol
• IEC 61850-9-2LE communication protocol
• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol
Several protocols can be combined in the same IED.
IEC 61850-8-1 communication protocol
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in
PCM600. The IED is equipped with single or double
optical Ethernet rear ports (order dependent) for IEC
61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the electrical
Ethernet front port. IEC 61850-8-1 protocol allows
intelligent electrical devices (IEDs) from different
vendors to exchange information and simplifies system
engineering. IED-to-IED communication using GOOSE
and client-server communication over MMS are
supported. Disturbance recording file (COMTRADE)
IEC13000239-2-en.vsd
uploading can be done over MMS or FTP.
IEC 61850-9-2LE communication protocol
Single optical Ethernet port communication standard
IEC 61850-9-2LE for process bus is provided. IEC
61850-9-2LE allows Non Conventional Instrument
Transformers (NCIT) with Merging Units (MU) or stand
alone Meging Units to exchange information with the
IED and simplifies SA engineering.
LON communication protocol
Existing stations with ABB station bus LON can be
extended with use of the optical LON interface. This
allows full SA functionality including peer-to-peer
messaging and cooperation between the IEDs.
SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
Monitoring Systems SMS.
M11344-3 v11
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple
substation automation systems including equipment
from different vendors. Disturbance files uploading is
provided.
1MRK 511 361-BEN D
M14815-3 v12
M14787-3 v12
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v2
SEMOD120140-5 v2
SEMOD120134-5 v1
SEMOD120137-5 v3