Table 11. AC input and output (continued)
Table 12. Weights and dimensions (UPS)
Model (UPS)
5594-5KX
5594-6KX
Table 13. Weights and dimensions (EBM)
Model (EBM)
5594-6BX
Table 14. Environmental and safety standards
EMC certifications
EMC (Emissions) - for output
cable < 10m
EMC (Immunity)
Agency markings
5594-5KX
230VAC, 5000VA, 4500W, 21.7A;
240VAC, 5000VA, 4500W, 20.8A
Dimensions D x W x H (mm / inch)
722 x 440 x 130 (28.4 x 17.3 x 5.1)
685 x 440 x 130 (27.0 x 17.3 x 5.1)
Dimensions D x W x H (mm / inch)
645 x 440 x 130 (25.4 x 17.3 x 5.1)
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
th
UL 1778 4
CSA 22.2
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
FCC part 15 Class A
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
CE / cULus / NOM
5594-6KX
230VAC, 6000VA, 5400W, 26.1A;
240VAC, 6000VA, 5400W, 25.0A
Weight (lb / kg)
106 / 48
106 / 48
Weight (lb / kg)
150 / 68
Appendix A. UPS model specifications