Lenovo RT5.0kVA Installation And User Manual page 25

3u rack or tower ups
Table of Contents

Advertisement

Battery settings
Submenu
Bypass standby
Automatic battery test
Low battery warning
Restart battery level
Battery charge mode
External battery
Deep discharge protection
Available settings
[Enabled] [Disabled]
Define if output is powered
from Bypass in Standby
mode.
In constant charge mode:
[No test] [Every day] [Every
week] [Every month]
In ABM cycling mode:
[No test] [Every ABM cycle]
[0%] ... [100%]
The alarm triggers when
the set percentage of
battery-pack capacity is
reached during back-up
time.
[0%] ... [100%]
If set, automatic restart
will occur only when
percentage of battery
charge is reached.
[ABM cycling] [Constant
charge]
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
[Yes] [No]
If set to Yes, the UPS
automatically prevents
batteries from deep
discharge by adapting end
of back-up time voltage
threshold. Warranty void if
set to No.
Default settings
[Disabled]
[Every ABM cycle]
[20%]
[0%]
[ABM cycling]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
[Yes]
13
.