F u n c .
N a m e
C o d e
C101
Up/Down memory mode
selection
Reset selection
C102
C103
Restart mode after reset
UP/DWN clear mode
C104
EO gain adjustment
C105
C106
AM gain adjustment
C109
AM bias adjustment
Overload warning level 2
C111
Output [11] on delay
C130
C131
Output [11] off delay
C132
Output [12] on delay
Output [12] off delay
C133
Relay output on delay
C140
Relay output off delay
C141
C142
Logic output 1 operand A
C143
Logic output 1 operand B
" C " F u n c t i o n
D e s c r i p t i o n
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
00Clear last frequency (return to
default frequency F001)
01Keep last frequency adjusted
by UP/DWN
Determines response to Reset
input [RS].
Four option codes:
00Cancel trip state at input signal
ON transition, stops inverter if
in Run Mode
01Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02Cancel trip state at input ON
transition, no effect if in Run
Mode
03Clear the memories only
related to trip status
Determines the restart mode after
reset is given, three option codes:
00Start with 0 Hz
01Start with freq. matching
02Start with active freq. matching
Freq. set value when UDC signal is
given to the input terminal, two
option codes:
000 Hz
01Original setting (in the
EEPROM memory at power
on)
Set range is 50 to 200%
Set range is 50 to 200%
Set range is 0 to 100%
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 s.
Set range is 0.0 to 100.0 s.
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
72
D e f a u l ts
Run
Mode
I n i t i a l
Edit
d a ta
*
1
00
00
*
00
1
*
1
00
100.
100.
0.
Rated current
x 1.15
*
1
0.0
*
1
0.0
*
1
0.0
*
1
0.0
*
1
0.0
*
1
0.0
*
1
00
*
1
00
U n i ts
-
-
%
%
%
A
s
s
s
s
s
s