Download Print this page

Hitachi WJ200 Series Quick Reference Manual page 42

Hide thumbs Also See for WJ200 Series:

Advertisement

Using Intelligent Output Terminals
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter outputs
a signal on that terminal when it is in Run
Mode. The output logic is active low, and is
the open collector type (switch to ground).
Option
Terminal
Code
Symbol

RUN
Valid for outputs:
Required settings
Notes:
 The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter . The start frequency
is the initial inverter output frequency when it turns
ON.
 The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name
Run Signal
11, 12, AL0 – AL2
(none)
[FW,RV]
Output
frequency
Run
signal
State
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example for terminal [11]
Inverter output
terminal circuit
Example for terminal [AL0], [AL1], [AL2]
Inverter logic
circuit board
36
1
0

start freq.
ON
Description
RUN
CM2
RY
RUN
AL0
AL1
AL2
Power
Load
supply
t
11

Advertisement

loading