F u n c .
N a m e
C o d e
b165
Ex. operator com. loss action
Data Read/Write select
b166
Inverter mode selection
b171
Initialization trigger
b180
(*)
b190
Password Settings A
b191
Password authentication A
Password Settings B
b192
b193
Password authentication B
Electronic thermal subtraction
b910
function selection
Thermal subtraction time
b911
Thermal subtraction time
b912
constant
Thermal accumulation gain
b913
When 01 is set on b180, and SET key is pressed, initialization starts immediately and there is
(*)
not any way to restore the previous parameter setting. WJ200 doesn't have a method to
trigger the initialization by key action as the other Hitachi inverter models have.
" b " F u n c t i o n
D e s c r i p t i o n
Five option codes:
00Trip
01Trip after deceleration to a stop
02Ignore
03Coasting (FRS)
04Decelerates to a stop
00 Read/Write OK
01 Read/Write Disable
Three option codes:
00No function
01Std. IM (Induction Motor)
03PM (Permanent Magnet Motor)
This is to perform initialization by
parameter input with b084, b085
and b094. Two option codes:
00Initialization disable
01Perform initialization
0000(Invalid Password)
0001-FFFF(Password)
0000-FFFF
0000(Invalid Password)
0001-FFFF(Password)
0000-FFFF
00...OFF
01...Linear subtraction:
pre-fixed ratio
02...Linear subtraction:
ratio set in b911
03...Subtraction with first-order
lag filter: ratio set in b912
0.10 to 100000.00[s]
(upper four digits are shown)
Out of warranty when setting less
than initial value (600[s])
[this function is valid when electronic
thermal protection selection
(b910)=02]
0.10 to 100000.00[s]
(upper four digits are shown)
Out of warranty when setting less
than initial value (120[s])
[this function is valid when electronic
thermal protection selection
(b910)=03]
1.0 to 200.0 [%]
Out of warranty when setting less
than initial value (100[%])
67
Run
D e f a u l ts
Mode
I n i t i a l
U n i ts
Edit
d a ta
02
-
*
1
00
-
00
-
00
-
0000
-
0000
-
0000
-
0000
-
*
00
-
1
*
600.00
s
1
*
120.00
s
1
*
1
100.0
%