Download Print this page

Hitachi WJ200 Series Quick Reference Manual page 64

Hide thumbs Also See for WJ200 Series:

Advertisement

F u n c .
N a m e
C o d e
A153
Curvature of EL-S-curve at the
end of deceleration
Deceleration hold frequency
A154
A155
Deceleration hold time
PID sleep function action
A156
threshold
A157
PID sleep function action delay
time
A161
[VR] input active range start
frequency
A162
[VR] input active range end
frequency
A163
[VR] input active range start
A164
[VR] input active range end
A165
[VR] input start frequency
select
" A" F u n c t i o n
D e s c r i p t i o n
Range is 0 to 50%
Sets the frequency to hold
deceleration, range is 0.0 to
400.0Hz
Sets the duration of deceleration
hold, range is 0.0 to 60.0 s.
Sets the threshold for the action,
set range 0.0~400.0 Hz
Sets the delay time for the
action, set range 0.0~25.5 s.
The output frequency
corresponding to the [VR] input
range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the [VR] input
range ending point,
range is 0. to 400.0 Hz
The starting point (offset) for the
[VR] input range,
range is 0. to A164 value (%)
The ending point (offset) for the
[VR] input range,
range is A163 value to 100.(%)
Two options; select codes:
00Use offset (A161 value)
01Use 0Hz
58
D e f a u l ts
Run
Mode
I n i t i a l
U n i ts
Edit
d a ta
10.
*
1
0.0
*
1
0.0
*
0.00
1
*
0.0
1
*
1
0.00
*
1
0.00
*
0.
1
*
100.
1
*
1
01
%
Hz
s
Hz
s
Hz
Hz
%
%

Advertisement