Terminal Modules
6.8 Terminal Module TM150
6.8.4
Meaning of the LED
Table 6-59
Meaning of the LEDs at the Terminal Module TM150
LED
Color
READY
–
Green
Orange
Red
Green/
red
Green/
orange
or
red/
orange
194
Status
Description, cause
Off
The electronics power supply is missing or outside the permis‐
sible tolerance range.
Continu‐
The component is ready for operation and cyclic DRIVE-CLiQ
ous light
communication is taking place.
Continu‐
DRIVE-CLiQ communication is being established.
ous light
Continu‐
This component has at least one fault.
ous light
Remark:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Flashing
Firmware is being downloaded.
light
0.5 Hz
Flashing
Firmware has been downloaded.
light
The system waits for POWER ON.
2 Hz
Flashing
Component recognition via LED is activated (parameter
light
p0154=1).
2 Hz
Remark:
Both options depend on the LED status when component rec‐
ognition is activated.
Remedy
Check the power sup‐
ply.
–
–
Remove and acknowl‐
edge the fault.
–
Carry out a POWER ON.
–
Control Units and additional system components