Connectors - ABB Relion Series Product Manual

Hide thumbs Also See for Relion Series:
Table of Contents

Advertisement

670/650 series and SAM600-IO IEC
IED
RXME 1
-
+
+
IEC06000064 V2 EN-US
Figure 9.
RXME 1 used as a trip contact re-enforcement
When single pole tripping is used one RXME 1 is required
per phase and of course per subsystem in redundant
systems.
Lock-out can be arranged with RXMD 1 remanence relay
activated from binary outputs on IED and possible other
protection relays required to activate lock-out, see figure 10.
The contact of RXMD 1 is connected to open the closing
circuit to the breaker closing coil. Another contact can be
used to light-up a lamp push button to have indication of the
lock-out and then reset with the push-button. It is
recommended to avoid trip contact latching as this will
mean problem for example with trip circuit supervision and
further at failing breaker, mean that the trip coil is burnt and
the trip coil DC supply is tripped. The most important is to
prevent that the breaker is closed at persistent faults.
IED
+
+
+
External
Close
IEC06000231 V2 EN-US
Figure 10.
Lock-out using a RXMD 1 relay
For ordering codes see section
reference to more detailed information.
RXME 1
IEC06000065 V1 EN-US
Figure 11.
RMXE 1 and RXMD 1 relays
10
Breaker
L1
L2
L3
xx06000064-2-en.vsd
RXMD 1
-
Breaker
-
+
xx06000231-2-en.vsd
"Related documents"
RXMD 1
xx06000057.ep
© 2017 - 2021 Hitachi Power Grids. All rights reserved.
Push button and selector switch
The push button is available with or without pilot lamp and
T
with one or two buttons. It is used to reset the lock-out
C
relays when an external independent lock-out and lock-out
indications is required. The push button unit can also be
used as a local selector of Auto-Reclose operation when
this is required to be done locally as well as through
communication.
The selector switch is available with two or three fixed
positions and with different contact combinations. Selector
switch can e.g. be used as Local/Remote selector or as a
local selector of Auto-Reclose operation. See section
"Related documents"
information.
IEC06000059 V1 EN-US
Figure 12.
Push button and selector switch
Supervision relay
The relay RXEM1 can be used to detect for example loss of
DC voltage supply or to detect open circuits. A typical
application is continuous supervision of a circuit breaker trip
C
circuit, including the breaker coil. See section
C
documents"
for reference to more detailed information.
for
xx06000060.eps
IEC06000060 V1 EN-US
Figure 13.
Supervision relay RXEM1

7. Connectors

The connectors are used for analogue signals and binary in-
and output signals.
Use the ferrules to connect two wires to the same terminal
point of a connector of screw compression type. Note that
2
1.5 mm
is the maximum dimension allowed on these wires.
An appropriate crimping tool is needed to apply the ferrule
1MRK 514 012-BEN K
for reference to more detailed
"Related
Hitachi Power Grids
SEMOD121142-4 v2
xx06000059.eps
SEMOD121154-4 v2
M2006-3 v3

Advertisement

Table of Contents
loading

This manual is also suitable for:

670 series650 seriesSam600-io iec

Table of Contents