Troubleshooting
AF-650 GP & AF-600 FP
Bit (Hex)
Unit
PROFIBUS warning word (PB-53 Profibus
diagnose
Warning Word)
bit
00000001
160
Connection with DP-master is not ok
00000002
161
Unused
00000004
162
NDL (Network Data link Layer) is not ok
00000008
163
Clear data command received
00000010
164
Actual value is not updated
00000020
165
Baudrate search
00000040
166
PROFIBUS ASIC is not transmitting
00000080
167
Initialising of PROFIBUS is not ok
00000100
152
Drive is tripped
00000200
153
Internal CAN error
00000400
154
Wrong configuration data from PLC
00000800
155
Wrong ID sent by PLC
00001000
156
Internal error occurred
00002000
157
Not configured
00004000
158
Timeout active
00008000
159
Warning 34 active
AF-650 GP & AF-600 FP
Bit (Hex)
Comm. option STW (DR-84 Comm. Option STW)
00000001
parameters ok
00000002
configuration ok
00000004
clearmode active
00000008
baudrate search
00000010
waiting for parameterization
00000020
waiting for configuration
00000040
in data exchange
00000080
not used
00000100
not used
00000200
not used
00000400
not used
00000800
MCL2/1 connected
00001000
MCL2/2 connected
00002000
MCL2/3 connected
00004000
data transport active
00008000
not used
NOTE
DR-84 Comm. Option STW is not part of extended diagnostics.