E.g.: Plc Programming - GE AF-650 GP PROFINET Operating Instructions Manual

Table of Contents

Advertisement

Application Examples

9.4 E.g.: PLC Programming

In this example PPO type 6 is placed in the following Input/Output address:
Input address
Set-up
This network will send a start command (047C Hex) and a
reference (2000 Hex) of 50% to the frequency converter.
9
9
This network reads the motor torque from the frequency
converter. A new reference will be sent to the frequency
converter because the Motor Torque (86.0%) is higher than
the compared value.
This network reads the status on the digital inputs from the
frequency converter. If digital input 18 is On it will stop the
frequency converter.
50
256-257
258-259
260-261
Status word
MAV
Motor torque Digital input
PROFINET Operating Instruction
262-263
Output
address
Set-up
This network will reverse the motor when digital input 19 is
ON, because O-54 Reversing Select is programmed to Logic
AND.
This network will activate the relay 02.
130BA110.10
256-257
258-259
260-261
Control word
Reference
Not used
262-263
Not used

Advertisement

Table of Contents
loading

This manual is also suitable for:

Af-600 fp profinetAf-650 gpAf-600 fp

Table of Contents