Cold plate mounting (ACSM1-204Cx-xxxx-x, frames C and D only)

For cold plate cooling characteristics, see page 71.
1. Determine the locations for the four fixing points on the cold plate. The fixing
points of the regen supply module are shown in the dimension drawings on page
94
(frame C) or
2. Clean the surface of both the regen supply module bottom plate (1) and the cold
plate (2) using a cloth and methylated spirit.
3. Apply a thin, uniform layer of thermal compound (e.g. WPS II from Austerlitz
Electronic GmbH) over the entire area of the regen supply module bottom plate.
4. Use four M6 (with minimum length of 12 mm) screws to fasten the regen supply
module to the cold plate. Tighten the screws to 0.5 N·m (4.4 lbf·in). Wait for at
least five minutes to allow the thermal compound to spread out evenly.
5. Tighten the mounting screws to a final torque of 3 N·m (26.5 lbf·in). Wipe off
excess thermal compound.
96
(frame D).