1. First startup flowchart
Start
Tap Start on the home screen.
After tapping Yes, the barcode and the
verification code are shown on the screen.
Open the Service Expert app.
Tap StartUp > Offline Activation on app.
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Enter. The screen turns to Wizard
No
Refrigerant is
fully charged?
Tap No on the Wizard Startup screen to
exit wizard startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm.
Charge the remaining amount of
refrigerant from low-pressure needle
valve.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home
Choose Maint > Wizard Startup to enter
wizard startup.
Go to step 2.
Startup.
Yes
screen.
2. Wizard startup flowchart
Start
Precautions
Yes
Select
Commissioning
items
Indoor fan
commissioning
Success
Electric heater
commissioning
Success
Humidifier
commissioning
Condensate
pump
commissioning
Outdoor fan
commissioning
Cooling system
commissioning
End
Tap Yes
on Wizard
Startup
screen to
If a water-cooled module is
enter
installed outdoors, outdoor fan
wizard
commissioning is not
startup.
implemented.
29
No
Fail
Commissionin
g interrupted
(Handle the
fault by
Fail
referring to
the tips
displayed on
the home
Fail
screen.
Perform
wizard startup
after the
Fail
handling.)
Fail

Advertisement