CAN Teamwork + FE Monitoring
Networking Teamwork
Protocol
CAN
One teamwork network supports a
maximum of 32 units. On the
Teamwork Settings screen of the
Description
display modules of the first and last
units, set Enable teamwork CAN
resistor to Yes.
Customers can purchase Huawei's switch and NetEco for the monitoring system.
FE Teamwork + RS485 Monitoring
Networking Teamwork Monitoring
Protocol
MAC_CAN
A teamwork
network
Description
supports a
maximum of
16 units.
Modbus-TCP
It takes 3 x n seconds to collect data from n units. If the time required
for the host to collect data from all units does not meet the
performance requirements, group the units.
If units are not grouped (n = 1), set RS485 monitoring grouping to
Enable on the Modbus Settings screen for each unit.
If units are grouped (n > 1; recommended: n ≤ 4), set RS485
monitoring grouping to Enable on the Modbus Settings screen
for the unit with the COM/FE port connected. Retain the default
setting (Disable) for other units.
Monitoring
Modbus-TCP/SNMP
-