Huawei NetCol5000-A050 Quick Manual page 2

In-row air cooled smart cooling
Hide thumbs Also See for NetCol5000-A050:

Advertisement

2
Onsite Preparations
Man-
Refrigerant
datory
pipe
Water pipe Humidifier water inlet pipe (optionally configured for the humidifier and the
Cable
specificati-
ons
Optio
Cable and
nal
base
Gas pipe requirements: outer diameter of 7/8 inch (22.22 mm) ; thickness of
1.2 mm; operating pressure ≥ 4.5 MPa
Liquid pipe:
L ≤ 60 m: outer diameter of 5/8 inch (15.88 mm) ; wall thickness of 1.0 mm;
operating pressure > 4.5 MPa
60 m < L ≤ 100 m: outer diameter of 3/4 inch (19.05 mm) ; wall thickness of
1.0 mm; operating pressure > 4.5 MPa
Thermal insulation foam: thickness ≥ 9.2 mm
Oil trap and inverted trap, and refrigerant pipe supports
humidifier hose is provided for the smart cooling product)
Rigid pipe: G 1/2 inch rigid pipe connector with external thread, rigid pipe
(such as PP-R pipe)
Hose: G 1/2 inch pagoda connector with external thread, hose (such as
EPDM pipe)
Humidifier water inlet pipe (optionally configured for the humidifier and the
humidifier hose is not provided for the smart cooling product): (PP-R and
other pipes) active connector: G3/4 inch internal thread, rigid pipe, elbow
Drainpipe:
Rigid pipe: BSPT 1/2 inch rigid pipe connector with external thread, rigid
pipe (such as PP-R pipe)
Hose: BSPT 1/2 inch pagoda connector with external thread, hose (such as
EPDM pipe)
Water-cooled module: cooling water supply and return pipes, steel pipes
having G1-1/2 inch connectors with external threads
Thermal insulation foam: thickness ≥ 9.2 mm
Indoor unit power cable: 5 x 10 mm
Outdoor unit power cable: 5 x 2.5 mm
Equipotential ground cable: 6 mm
Power cable for the water-cooled module: 3 x 1.5 mm
(Optional) Power cable of the low temperature component: 2 x 1.5 mm
(Optional) Signal cable between the indoor and outdoor units: 3 x 1.5 mm
Electrical power cable, 300 V, SJTW, 3 x 16 AWG, black (three cores: black,
white, and green), 10 A, shielded outdoor cable, UL
Temperature and humidity (T/H) sensor outside the cabinet and cable;
determined based on scenarios: indoor unit base, outdoor unit support or
concrete base, and water-cooled module concrete base
2
(Do not use the N wire onsite.)
2
outdoor copper cable
2
1. The signal cable for the indoor and outdoor units
is mandatory when the outdoor unit is equipped
with an intelligent temperature control
monitoring board.
2. The shield layer of signal cable must be grounded.
3. Do not use shielded cables as outdoor unit power
cables.
2
2
2
2
,